VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-14
Hz
Freq.
Motor
Speed
Stops according
to deceleration
time
Time
Hz
Freq.
Motor
Speed
Free running
to stop
Time
Operation
command
ON
ON
OFF
OFF
Ramp
Coast
Note: The motor stop method is usually determined by the characteristics of the motor load
and frequency of stops.
2 - 03 PWM Carrier Frequency Selections Factory Setting: d 10
Settings d 03 fc= 3KHz Unit: 1KHz
d 04 fc= 4KHz
d 05 fc= 5KHz
to
d 10 fc= 10KHz
This parameter can set the carrier frequency of PWM output.
Carrier
Frequency
Acoustic Noise
Electromagnetic
Noise, Leakage
Current
Heat
Dissipation
3KHz
10KHz
Significant
Minimal
Minimal
Significant
Minimal
Significant
From the above table, we see that the carrier frequency of PWM output has a significant
influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic
noise to the motor.