5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-3
Display Number Represented
999 The absence of a decimal point indicates a three–digit integer.
99.9
A signal decimal point between the middle and the right-most numbers is a true
decimal point; it separates ones and tenths as in “30.5” (thirty and one-half).
999.
A single decimal point after the right-most numbers is not a true decimal point,
instead it indicates that a zero follows the right-most number. For example,
the number 1230 would be displayed as “123.”
99.9.
Two decimal points (one between the middle and the right-most numbers, and
one after the right-most number) are not true decimal points; instead they
indicate that two zeros follow the right-most number. For example, the
number 34500 would be displayed as “34.5.”.
0 - 06 Software Version Factory Setting: d #.#
Setting None
The software version is read-only that stores the version number of VFD-S series
software.
0 - 07 Password Input Factory Setting: d 0
Settings d 0 to d 999 Unit: 1
Pr.0-07 and Pr.0-08 work together to provide data security for the AC drive. When
Pr.0-08 is set to a value other than 0, a password must be entered to alter the values of
parameters. The password is the number set in Pr.0-08, which ranges from 1 to 999.
Pr.0-07 is where the password is entered to allow parameter values to be altered.
Display states:
d 0: no password / correct password has been input
d 1: parameters are locked