Delta Electronics Network Device VFD-S Dokumentacja Strona 80

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 130
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 79
5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-63
A - 11 Revival Frequency Factory Setting: d0.0
Settings d0.0 to d400Hz
A - 12 Dwell (sleep) Period Factory Setting: d0.0
Settings d0.0 to d650 seconds
! These parameters determine Dwell (sleep) functions of the AC drive. If the command
frequency falls below the Dwell frequency, for the specified time in Pr. A-12, then the
drive will shut off the output and wait until the command frequency rises above Pr. A-11.
Please see the below diagram.
A-11
A-10
A-12
0Hz
Dwell (sleep) Function
Dwell (sleep) Period
Dwell (sleep) Frequency
Revival Frequency
Frequency Command
A
ctual running
output frequency
A - 13 PID – Felhasználó által beállított Factory Setting: d0.0
Settings d0.0 to d400
! When parameter A-13 is set to 0, what F and H display is the actual value of setting
frequency and output frequency. When this parameter is not set to 0, the display value of
F and H = actual value !A-13/1-00. To set frequency with panel, communication, VR, AVI
or ACI need to set according to the display value. For example, when 1-00=60.0Hz, if
A-13 is set to 30.0 Hz, it means when the actual value of frequency is 30.00 Hz, the
display value will be 15.0 Hz . If you want to let drive run at 10.0Hz, the frequency
command must be 5.0 Hz. But the setting frequency of parameters, such as Max.
operation frequency, 1
st
speed and etc., they are still needed to set with actual value.
Przeglądanie stron 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 129 130

Komentarze do niniejszej Instrukcji

Brak uwag