5.4 Group 3: Kimeneti Funkciók Paraméterezése
3 - 00 Analóg kimeneti Jel Factory Setting: d 0
Settings d 0 Analog frequency meter (0 to Maximum Output Frequency).
d 1 Analog current meter (0 to 250% of the rated AC drive
current).
! This parameter selects either Output Frequency or current to be displayed using the 0
to10V AFM output.
3 - 01 Analóg kimenet érték erősítése Factory Setting: d100
Settings d 1 to d 200% Unit: 1%
The parameter can be set during operation.
! The parameter sets the voltage range of the analog output signal at terminals AFM, that
corresponds with either the output frequency or the output current of the VFD.
+-
AFM
GND
nalog Frequency Meter
+-
AFM
GND
nalog Current Meter
The analog output voltage is directly proportional to the output frequency of the AC drive. With
the factory setting of 100%, the Maximum Output Frequency (Pr.1-00) of the AC drive
corresponds to +10VDC analog voltage output. (The actual voltage is about +10VDC, and can
be adjusted by Pr.3-01).
The analog output voltage is directly proportional to the output current of the AC drive. With the
factory setting of 100%, the 2.5 times rated current of the AC drive corresponds to +10VDC
analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by Pr. 3-01)
Note: Voltmeter specification: The sourcing capability of the output is limited to 0.21mA.
Sourcing voltage: 10V. Output resistance: 47kΩ.
If the meter reads full scale at a voltage less than 10 volts, then Pr.3-01 should be set by
the following formula:
Pr.3-01 = ((meter full scale voltage)/10) ×100%
For example: When using the meter with full scale of 5 volts, adjust Pr.3-01 to 50%.