Example 8:
In this example, the option of anti-slope is shown. Anti-slope is used in an application where
control of pressure, temperature, or flow is needed. Under a high pressure or flow situation, a
sensor will generate a large signal such as 20 mA or 10V. With anti-slope enable, the large
signal will slow or stop the AC drive
Hz
0V
4mA
10V
20mA
30
0
60
Potentiometer Scale
Max.
Output
Freq.
60Hz
Pr.1-00
0Hz
0V
4mA
10V
20mA
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=60Hz--Potentiometer bias freq.
Pr.4-01=1 -- bias polarity
Pr.4-02=100% -- pot. freq. gain
Pr.4-03=1 -- pot. REV. motion enable
anti-slope
4 - 04 Multi-function Input Terminal (M0, M1) Factory Setting: d 1
Settings d 0 to d 26
4 – 05 Multi-function Input Terminal (M2) Factory Setting: d 6
4 – 06 Multi-function Input Terminal (M3) Factory Setting: d 7
4 – 07 Multi-function Input Terminal (M4) Factory Setting: d 8
4 – 08 Multi-function Input Terminal (M5) Factory Setting: d 9
Settings d 0,d 4 to d 26
Parameters & Functions table:
Value Function Value Function
d 0 Parameter Disable
d 1 M0: FWD / STOP, M1: REV / STOP
d14
External Base Block (N.C.)
(Normally Close Contact Input)
d 2 M0: RUN / STOP, M1: FWD / REV d15 Increase Master Frequency
d 3
3-Wire Operation Control mode (M0,
M1, M2)
d16 Decrease Master Frequency
d 4 External Fault (Normally Open) d17 Run PLC Program
d 5 External Fault (Normally Closed) d18 Pause PLC Program
d 6 External Reset d19 Counter Trigger Signal
d 7 Multi-Step Speed Command 1 d20 Counter Reset
d 8 Multi-Step Speed Command 2 d21
Select ACI / Deselect AVI (the priority is
higher than Pr. 2-00 and d26)
d 9 Multi-Step Speed Command 3 d22 Disable PID function
d10 Jog operation d23 JOG FWD
d11 Acceleration/Deceleration Speed Inhibit d24 JOG REV
d12
First or Second Acceleration or
Deceleration Time Selection
d25
The source of master frequency is AVI. (The
priority is higher than Pr. 2-00 and d26)
d13
External Base Block (N.O.)
(Normally Open Contact Input)
d26
The source of master frequency is ACI.
(The priority is higher than Pr. 2-00)