Delta Electronics Network Device VFD-S Dokumentacja Strona 29

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 130
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 28
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-12
5.3 Group 2: Operation Method Parameters
2 – 00 A frekvencia parancs kiadásának forrása Factory Setting: d 0
Settings d 0 Master Frequency input determined by digital keypad.
(record the frequency of power loss and it can do analog
overlap plus)
d 1 Master Frequency determined by analog signal DC 0V-10V
(external terminal AVI). (won’t record the frequency of power
loss and it can’t do analog overlap plus)
d 2 Master Frequency determined by analog signal DC 4mA -
20mA (external terminal AVI). (won’t record the frequency of
power loss and it can’t do analog overlap plus)
d 3 Master Frequency determined by Potentiometer on the
digital keypad. (won’t record the frequency of power loss
and it can do analog overlap plus)
d 4 Master Frequency operated by RS-485 serial
communication interface and record frequency of power
loss. (record the frequency of power loss and it can do
analog overlap plus)
d 5 Master Frequency operated by RS-485 serial
communication interface and won’t record frequency before
power loss. (won’t record the frequency of power loss and it
can do analog overlap plus)
! This parameter sets the Frequency Command Source of the AC drive.
If the Frequency Command Source is external (DC 0 to +10V or 4 to 20mA), please
make sure the (AVI) terminal jumper is in the proper position as shown below.
! Position of jumper: Please open the top cover. It is at the lower-left corner of the panel.
The jumper J1 determines the type of external analog input, either DC voltage signal or
current signal.
Przeglądanie stron 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 129 130

Komentarze do niniejszej Instrukcji

Brak uwag