Ethernet Communication Module DVPEN01-SL
CR value Data exchange status
0 The data have not been received.
1 The data exchange is in progress.
2 The data exchange is successful.
3 The data exchange fails.
CR#117, 118: MODBUS TCP destination IP address
Explanations:
Setting the destination IP address in MODBUS TCP mode
See explanations on CR#70 and #71 for more information.
CR#119: MODBUS TCP data length
Explanations:
Setting the length of communication data in MODBUS TCP mode
Length for 8-bit mode: K1~K100
Length for 16-bit mode: K1~K200.
CR#120~219: MODBUS TCP data buffer
Explanations:
Buffer for transmitted/received data in MODBUS TCP mode
CR#251: Error code
Explanations:
Table of error codes:
Bit No. Error
b0 The network is not yet connected.
b1 Incorrect IP address setting
b2
CR#13 is set as “transmitting data”, but the data exchange
is forbidden.
b3
CR#13 is set as “transmitting data”, but the data exchange
mode has not yet been enabled.
b4 NTP-Server connection fails.
b7 SMTP-Server connection fails.
b8 DHCP has not obtained the correct network parameter.
RTU Mapping
CR#15: Enabling glag for the RTU mapping
Explanations:
1: Enable
0: Disable
Default=0
Firmware V2.0 and later versions support the RTU mapping.