5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-71
Definition Parameter Address Function
Command toward
the drive
Bit8~9 00B: no function
01B: operation commands
controlled by the digital
keypad
10B: operation commands
controlled by the RS485
communication or the external
terminal command (Pr. 02-01)
11B: source change for the
operation command
Bit6~7 Reserved
2000H
Bit12~15 Reserved
2001H frequency/torque command
2002H Bit0 1: E.F. ON
Bit1 1: RESET command
Bit2~15 Reserved
Monitor the status
of the drive
2100H Error code: refer to Pr. 06-10~06-13
2119H Bit 0 1: RUN command
Bit 1 1: RUN state
Bit 2 1: JOG command
Bit 3 1: REV command
Bit 4 1: REV state
Bit 8 1: master frequency source from
the communication interface
Bit 9 1: master frequency source comes
from the input of
/plc/muit/avi/aci/aui through the
analog/external terminal signals
Bit 10 1: operation command from the
communication
interface/external terminals
Bit 11 1: parameter locked
Bit 14~15 Reserved
2102H frequency/torque command (F)
2103H output frequency/torque (H)