2 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-1CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the s
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6711 - 02 Multiple Motors Control Factory Setting: 01 Settings 01~04 When this param
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-68 If multi-function input terminals (04-00 to 04-07) are set to 27 to 31, the correspond
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-69 After power supply of motor is not from AC drive, the motor will coast to stop acco
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-70H>(11-06)HYESNONONOYESNOYESYESH<(11-08)T1=T1+1T2=T2+1T1=0T2=0NOFFH0==T2>(11-05)T
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-7111 - 07 Enter Sleep Process Time Factory Setting: 0.0 Settings 0.0~3600.0sec Unit:
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-7211 - 10 Treatment of Fixed Amount Circulation Malfunction Factory Setting: 00 Settings
6 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 6-1CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state ele
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED This page intentionally left blank.
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-1CHAPTER 7 Troubleshooting and Fault Information The AC drive has a comprehensive faul
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-2Fault Name Fault Descriptions Corrective Actions The AC drive temperature sensor detects
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-22.2 Installation CAUTION The control, power supply and motor leads must be laid separatel
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-3Fault Name Fault Descriptions Corrective Actions OC hardware error Return to the fact
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-4Fault Name Fault Descriptions Corrective Actions Analog Signal Error 1. Check ACI wiring
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-5Fault Name Fault Descriptions Corrective Actions Ground fault: The AC drive output is
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-6Fault Name Fault Descriptions Corrective Actions Fan 1, 2, 3 fault (150~300HP) Remove any
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-1CHAPTER 8 PARAMETER SUMMARY Group 0 AC Drive Status Parameter Parameters Functions S
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-2 Parameters Functions Settings Factory SettingCustomer 00-02 AC Drive Status Indication
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-3Group 1 Basic Parameter (Twice the value for 460V class) Parameters Functions Setting
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-4Group 2 Digital Output/Input Parameter Parameters Functions Settings Factory SettingCust
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-5 Parameters Functions Settings Factory SettingCustomer 02-07 Loss of ACI Signal 00:
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-6Group 3 Output Function Parameters Parameters Functions Settings Factory SettingCustomer
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconn
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-7 Parameters Functions Settings Factory SettingCustomer 37: PLC program operation
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-8Group 4 Input Function Parameters Parameters Functions Settings Factory SettingCustomer
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-9 Parameters Functions Settings Factory SettingCustomer 04-15 ACI1 Minimum frequency (
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-10Group 5 Multi-step Speed Frequency Parameters Parameters Functions Settings Factory Set
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-11 Parameters Functions Settings Factory SettingCustomer 05-28 Time Duration Step 12
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-12Group 6 Protection Function Parameters (Twice the value for 460V class) Parameters Funct
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-13 Parameters Functions Settings Factory SettingCustomer 05: oL1 (over load 1) 06: EF
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-14Group 7 AC Drive and Motor Parameters Parameters Functions Settings Factory SettingCust
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-15Group 8 Special Parameters (Twice the value for 460V class) Parameters Functions Set
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-16Group 9 Communication Parameters Parameters Functions Settings Factory SettingCustomera
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-23.1 Basic Wiring Diagram Users must connect wires according to the following circuit diagr
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-17 Parameters Functions Settings Factory SettingCustomera09-06 Communication Operation
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-18Group 10 PID Controls Parameters Functions Settings Factory SettingCustomer 10-00 Inp
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-19Group 11 Fan and Pump Control Parameters Parameters Functions Settings Factory Setti
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED This page intentionally left blank.
A VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-1Specifications Voltage Class 230V Class Model Number VFD-_ _ _F23_ 007 015 022 037 055
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-2Other Functions AVR, 2 kinds of S-Curve, Over-Voltage, Over-Current Stall Prevention, Faul
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-1 ACCESSORIES B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Pl
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-2NOTE 1. Please select the brake unit and/or brake resistor according to the table. “-“ me
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-3 B.1.1 Dimensions and Weights for Brake Resistors (Dimensions are in millimeter) Order
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-4Order P/N: BR500W030, BR500W100, BR1K0W020, BR1K0W075 TYPE L1 L2 H D W MAX. WEIGHT(g)BR50
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-3*RS-485R(L1)S(L2)T(L3)NFBRSTRBRC+1 +2SAOFFONMCMCE1:+EV2:GND3:SG-4:SG+5:NC6:NCMI1MI2MI3M
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-5 B.1.2 Specifications for Brake Unit Voltage Class 230V Series 460V Series Model Numb
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-6B.1.3 Dimensions for Brake Unit (Dimensions are in millimeter[inch]) Figure 1: VFDB2015, V
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-7 Figure 2: VFDB4132 VFDB4132CHARGE ACT OC OH
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-8B.2 AMD-EMI Filter Cross Reference AC Drives EMI Model NumberVFD007F23A/H, VFD015F23A/H,
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-9 Remove any paint on metal saddle for good ground contact with the plate and shielding
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-10B.3 AC Reactor AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase Inductance (mh
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-11 AC Output Reactor Recommended Value 230V, 50/60Hz, 3-Phase Inductance (mH) kW HP Fund
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-12B.4 Non-fuse Circuit Breaker Chart The fuse should comply with UL248 and the breaker shou
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-13B.5 Fuse Specification Chart Smaller fuses than those shown in the table are permitted
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-14B.6 PU06 B.6.1 Description of the Digital Keypad VFD-PU06 UFHVFD-PU06JOGRUNRESETSTOPLED
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-4Wiring for SINK mode and SOURCE mode JOG1/2 Accel/Decel switchMI7MI8 Sw1SinkSourceJO
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-15Display Message Descriptions The specified parameter setting. The actual value store
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-16B.7 Relay Card Specifications: 1. Screw Length (between RELAY CARD and Control Board): 8
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-17PCB-SUPPORTPCB-SUPPORT CONTROL-BOARDPCB-SUPPORTINSULATORRELAY-CARDSCREW M3*P0.5TORQUE=
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-18B.8 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (inch) Reco
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-1 DIMENSIONS Frame B HW1DH1WD1S2S1 UNIT: mm [inch] Frame W W1 H H1 D D1 S1 S2 B1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-2Frame C W1WH1HS2DD2D1S1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 S2 C1 200.0 [7.88] 185.
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-3 Frame D WW1HH1DS1D2D1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 D1 250.0 [9.84
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-4Frame E W1WH1H2HDS2D1S1D2S3 UNIT: mm [inch] Frame W W1 H H1 H2 D D1 D2 S1 S2 S3 E1 370.0 [
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-5 Frame G W1WH1HD1H2D2S2HJOGURUNMODEPROGRESETSTOPDATAJOGRUN STOP REVVFD-PU01FWDFS1DS3S4
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-6Frame H W1WH1HD1H2D2S2HJOGURUNMODEPROGRESETSTOPDATAJOGRUN STOP REVVFD-PU01FWDFS1DS3S4 UNIT
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-53.2 External Wiring R/L1S/L2T/L3U/T1V/T2W/T3B2-+/B1EEBRVFDBBREMI FilterPower SupplyFUSE
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-7 VFD-PU01 Unit: mm (inches) 6.5 [0.26]19.0 [0.75]110.0 [4.33]73.0 [2.87]97.0 [3.82]44.0
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-8KPF-CC01 Unit: mm (inches)
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-63.3 Main Circuit Connection Figure 1 for the main circuit terminals R(L1)S(L2)T(L3)RSTU(T1
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-7Mains power terminals (R/L1, S/L2, T/L3) Connect these terminals (R/L1, S/L2, T/L3)
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-8Terminals [+2/B1, B2] for connecting brake resistor and terminals [+2/B1, -] for connectin
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-93.4 Control Terminals +24VDCMSINK/NPN ModeMulti-functionInput TerminalInternal Circuit
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-10Terminal Symbols Terminal Functions Factory Settings +10V Potentiometer power source +10
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-113.5 Specifications for Power Terminals and Control Terminals Frame B +1+2B1-B2R/L1 S/L
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-12Frame D 3IMPOWER - ( ) ( ) + DC DC MOTORPower Terminals: R/L1, S/L2, T/L3, U/T1, V/T2,
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-13Frame G POWER DC(+)IMMOTORDC(-)3V/T2S/L2R/L1 +2T/L3 +1 U/T1 W/T3 Power Terminals: R/L1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-143.6 Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. ! CAUTION: Do not connect the AC
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1513. For the single-phase rated AC drives, the AC power can be connected to any two of
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-163.7 Motor Operation Precautions 1. When using the AC drive to operate a standard 3-phase
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-1CHAPTER 4 DIGITAL KEYPAD OPERATION This chapter describes the various controls and i
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-24.1 VFD-PU01 4.1.1 Description of the Digital Keypad VFD-PU01 UFHVFD-PU01JOGLED DisplayDi
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-3Display Message Descriptions Display the AC drive forward run status. The AC drive r
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-44.1.3 Operation steps of the Digital Keypad VFD-PU01 MODEMODEMODEMODEMODEMODE STARTUFHSele
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-54.2 KPF-CC01 For models of VFD-F (HVAC) series VFD007F43H; VFD015F43H; VFD022F43H; VFD0
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-6Display Message Description The output current present at terminals U, V, W. The specif
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS a: This parameter can be set during operati
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2Code AC Drive Status Explanation 26 FAnP Fan Power Fault 27 FF1 Fan 1 Fault 28 FF2 F
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3 This parameter displays output power factor. 00 - 09 Output Power (kW) Factory
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-45.2 Group 1: Basic Parameters 01 - 00 Maximum Output Frequency Factory Setting: 60.
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-501 - 04 Mid-point Voltage Factory Setting: 5.5/11.0 Settings 230V series: 0.1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6Output voltageOutput Frequency01-0201-0401-0601-0001-0701-0801-0101-05 01-03 01 - 09 Acc
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED Preface Thank you for choosing DELTA’s high-performance VFD-F Series. VFD-F Series are manu
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-701 - 19 JOG Frequency a Factory Setting: 6.00 Settings 0.0 Hz~120.00 Hz Unit:
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-801-23 Accel/Decel time unit Accel/Decel time range00 1 Sec 1~36000 Sec 01 0.1 Sec 0.1~
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-95.3 Group 2: Operation Method Parameters 02 - 00 Source of Frequency Command a Factory
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1002 - 02 Stop Method Factory Setting: 00 Settings 00:Stop = ramp to stop, E.F. (Extern
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-11 The Carrier frequency of the PWM output has a signification influence on the electr
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-12 02 - 06 Line Start Lockout Factory Setting: 01 Settings 00: Disabled 01: Enabled
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1302 - 09 Special Display a Factory Setting: 00 Settings 00: A displays output
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-14 If this parameter is set to 00: The AC drive will not store the last known master freq
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-155.4 Group 3: Output Function Parameters 03 - 00 Multi-function Output terminal 1 Fact
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-16Setting Functions Descriptions 21 Low voltage detection The corresponding output will
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED TABLE OF CONTENTS CHAPTER 1 RECEIVING AND INSPECTIONS 1.1 Nameplate Information ...
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-17 External relay specifications = 8A/250VAC or 5A/30VDC. Relay delay time is 5~10
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-18 Setting 04: 0-10V = 0.0 - output power factor 1.0 When using 0-20mA output, please
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-195.5 Group 4: Input Function Parameters 04 - 00 Multi-function Input terminal 1 Factor
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-20Setting Functions Descriptions 17 AVI(open), ACI1(close) External selection of the Maste
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-21 In noisy environments, it would be advantageous to verify the terminal status sever
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-22Please refer to the following diagram for more details: 04-1204-1604-1104-1504-1904-0904
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2304 - 21 Analog Input Delay AVI Factory Setting: 0.5004 - 22 Analog Input Delay ACI1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-245.6 Group 5: Multi-step Speed Frequency Parameters 05 - 00 1st Step Speed Frequency a Fa
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-25Example 1 (Pr.05-15 = 1): Execute one cycle of the PLC program. Its relative parameter
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-26Example 3 (Pr.05-15 = 3) Execute one cycle step by step: The example below shows how the
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4.2 KPF-CC01 ...
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-27123456789101112131415 0WeightsBit0=Forward1=ReverseDirection of Pr.05-001st speed for
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2805 - 17 Time Duration of 1st Step Speed Factory Setting: 0.005 - 18 Time Duration of
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2905-05FrequencyMaster Speed05-0005-0105-0205-0305-0405-0605-0705-0805-0905-1005-1105-12
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-305.7 Group 6: Protection Function Parameters 06 - 00 Over-voltage Stall Prevention Facto
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-31Over-current StallPrevention during acceleration06-01CurrentOutput frequencyOver-curre
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-32 This parameter selects the Over-torque Detection operation. If this parameter is s
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-331234560Hz or more50Hz10Hz5HzLoad factor(%)OperationTime(min)020406080100120140160180 2
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-34 10 Over current during acceleration (ocA) 11 Over current during deceleration (
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-35 This parameter allows the user to enter their password to unlock the Parameter Prot
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-365.8 Group 7: AC Drive and Motor Parameters 07 - 00 Identity Code of AC Drive Factory Se
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CHAPTER 8 SUMMARY OF PARAMETER SETTINGS ... 8 - 1 APPENDIX A S
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-37 This parameter is used with slip compensation Pr.7-04 to Pr.7-05 and electronic the
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-38 Unsuitable setting value may cause over compensation. 07 - 05 Rated Slip Frequency o
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-395.9 Group 8: Special Parameters 08 - 00 DC Brake Current Level Factory Setting: 00 S
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-40Output frequencyTimeDC Braking TimeONOFFRun/StopDC brakingcurrentlevelDC brakingtime duri
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4108 - 06 Speed Search Time Factory Setting: 0.5 Settings 0.1~5.0 Sec Unit: 0.1 Thi
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-42Master frequency commandOutput frequencyOutput voltageoutput currentSynchronization attai
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4308 - 10 Auto Restart Time after Fault Factory Setting: 600 Settings 00 to 60000 sec
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4408 - 18 Automatic Voltage Regulation (AVR) Factory Setting: 00 Settings 00: AVR function
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-455.10 Group 9: Communication Parameters 09 - 00 Communication Address a Factory Settin
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4609 - 06 Communication Operation Command 1 a Factory Setting: 00 Settings Bit0~1:
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-1CHAPTER 1 RECEIVING AND INSPECTION This VFD-F AC drive has gone through rigorous qual
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-47 If you set BB action by this parameter and you also need to disable BB action by th
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-48 (7 , E , 1 : 9-04=0, 9-05=04) 0123456StartbitEvenparityStopbit7-bit character10-bit ch
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-493. Communication Protocol 3.1 Communication Data Frame: ASCII mode: STX Start chara
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-50z Command code: 03H, read N words. The maximum value of N is 10. For example, reading pa
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-51z Command code: 06H, write a word For example, writing 6000(1770H) to address 0100H of
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-52z Command code: 08H, loop detection This command is used to test the communication condit
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-53ASCII mode: Command message: Response message: Error response messageSTX ‘:’ STX
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-543.4 CHK (check sum) ASCII mode: LRC (Longitudinal Redundancy Check) is calculated by sum
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-55Step 6: Repeat step 2 to 5 for the next 8-bit byte of the command message. Continue do
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-563.5 Address List The contents of available addresses are shown as below: Content Address
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-21.3 Series Number Explanation Production number3055F43AProduction model460V 3-PHASE
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-57Content Address Function 14: Under voltage (Lv) 15: EEPROM WRITE failure (cF1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-58Content Address Function 2102H Frequency command (F) 2103H Output frequency (H) 2104
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-59The explanation of exception codes: Exception code Explanation 01 Illegal function cod
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-605.11 Group 10: PID Control Parameters 10 - 00 Input Terminal for PID Feedback Factory Se
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-61 When this parameter is set to 01: when positive control, the deviation equation is
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-62 Output frequency of PID controller will filter by primary low pass function. This func
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-635.12 Group 11: Fan and Pump Control Parameters 11 - 00 V/f Curve Selection Factory Se
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-64 When Pr. 11-01 is set to 01 Time Circulation. Starts a motor, runs it for a fixed amou
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-65 When Pr. 11-01 is set to 02 “Fixed Amount Circulation” and adding relay card “RY-00
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-66 When Pr. 11-01 is set to 03 “Fixed Amount Control” and adding relay card “RY-00”, VFD-