03 - Comparison of Terminals between CP2000 & VFD-F
3-1
03 - Comparison of Terminals
VFD-F VFD-CP2000
Terminals
Terminal Function Factory Setting (NPN mode)
Terminals
Terminal Function Factory Setting (NPN mode)
+24V
Digital control signal common
(Source)
+24V 20mA +24V
Digital control signal common
(Source)
+24V±5% 200mA
DCM
Digital control signal common
(Sink)
Common for multi-function
input terminals
COM
Digital control signal common
(Sink)
Common for multi-function
input terminals
FWD Forward-Stop command
FWD Forward-Stop command
FWD-DCM:
ON: forward running
OFF: deceleration to stop
REV Reverse-Stop command
REV Reverse-Stop command
REV-DCM:
ON: reverse running
OFF: deceleration to stop
MI1 Multi-function input 1
Factory setting: Multi-step
speed command 1
MI1 Multi-function input 1
MI2 Multi-function input 2
Factory setting: Multi-step
speed command 2
MI2 Multi-function input 2
MI3 Multi-function input 3
Factory setting: Multi-step
speed command 3
MI3 Multi-function input 3
MI4 Multi-function input 4
Factory setting: Multi-step
speed command 4
MI4 Multi-function input 4
MI5 Multi-function input 5 Factory setting: RESET MI5 Multi-function input 5
MI6 Multi-function input 6 Factory setting: JOG MI6 Multi-function input 6
MI7 Multi-function input 7
Factory setting: Accel/Decel
prohibit
MI7 Multi-function input 7
MI8 Multi-function input 8
Factory setting: Accel/Decel
time switch 1
MI8 Multi-function input 8
Refer to parameters
02-01~02-08 to program the
multi-function inputs
MI1~MI8.
ON: the activation current is
6.5mA 11Vdc
OFF: leakage current tolerance
is 10µA 11Vdc
DCM Digital frequency signal common
EF External fault