Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-22 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
DOP series
9 pin D-SUB male (RS-232)
Controller
6 pin RJ11
Controller
9 pin D-SUB female
(RS-232)
RXD (2)
2
TXD (3)
GND (5)
3
5
Top View
NOTE
1) Device S
The unit of PLC internal memory is byte and Device S is read by the unit of byte. Therefore, we
recommend the user do not use two consecutive devices S as the read addresses or the interference will
occur. For example, when choosing two numeric input device, please use S24 and S26, do not use S24
and S25.