1http://www.delta.com.tw/industrialautomation/ DTC1000/2000 Temperature Controller User Manual Thank you very much for purchasing DELTA C Series Temp
10Address Setting Content Explanation 1035H Executing number of reading current pattern 0~7 1037H 1000 Upper-limit of proportional output 0~100%
11 6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit data as “0”) 081
12To Read Instruction To Read Response Message To Write Instruction To Write Response Message Machine address 01H 01H Machine address 01H 01HMachin
2 2 Auxiliary Output Groups 0: standard, 2 groups output, no auxiliary output 1: 1 group auxiliary output. Not available now. 2: 2 groups auxiliary
34 PRODUCT PROFILE AND OUTLINE DTC1000R/V/C/L 90.03.060.03.425.24.03.01234567891031112131. RUN/STOP switch 2. Wiring and Model name 3. DIN fix 4
4Note 1: an external 250Ω precision resistor is needed for current input. Note 2: factory setting: PT100 input. It is adjustable for linear input an
5PV0Dead band:deadband width:positiveDead band:deadband width:negativePV0OutputHeating CoolingSet PointOutputHeatingCoolingSet PointFigure 5: PID con
6value=0 with input range 0~1000, output will be 0mA or 0V. When read value=1000, output will be 20mA or 10V. Figure 7: RetransmissionOutput10V or 20
7SV Alarm Type Alarm Output Function value is lower than the setting value SV+(AL-L). 12 Hysteresis lower-limit alarm output: This alarm output o
8 Bit=0 means no password setting. Bit=1 means password is set (b0~b2). b3~b6 are used for displaying current password status. 9 SYNCHRONOUS COMM
9Address Setting Content Explanation Dual Loop output control are used 100FH 0 Dead band setting when Dual Loop output control are used -999~9999,