DTC1000/2000 Temperature Controller
User Manual
Thank you very much for purchasing DELTA C Series Temperature Controller. Please read this
instruction sheet before using your C series to ensure proper operation and please keep this
instruction sheet handy for quick reference.
1 Precaution
DANGER: ELECTRIC SHOCK!
DTC1000 is an OPEN-TYPE Process Control Equipment and DTC2000 is an OPEN-TYPE
Process Control Accessory. These devices are microprocessor-based temperature regulating
controllers which may be provide with normally closed and/or open contacts. They are
intended for installation completely within an overall panel or Process control Enclosure and
are used in heating or cooling applications. Please Install within a separate UL Listed
enclosure only, keep the enclosure away from airbome dust or high humidity and prevent
electric shock or sudden shock. Also, it is equipped with protective methods such as some
special tool or key to open the enclosure, so as to avoid the hazard to users or any damage to
the module.
1. Prevent dust or metallic debris from falling into the controller that will cause malfunction.
2. Do NOT modify or disassemble the controller.
3. Do NOT connect to “No Used” terminal.
4. Do not install and/or use the controller in places subject to:
(a) Dust or corrosive gases and liquid. (b) High humidity and high radiation. (c) Vibration and
shock. (d) High voltage and high frequency
5. Power off when wiring and changing an input sensor.
6. Be sure to use compensating wires that match the thermocouple types when extending or
connecting the thermocouple wires.
7. Shorten the wire when wiring a platinum resistance thermometer (RTD) to the controller and
separate power cable from load wires to prevent interference and conductive influence.
8. Make sure power cables and signals device are installed properly before power on; otherwise
serious damage may occur.
9. Do NOT touch the terminals or repair the controller when power on to prevent electric shock.
10. Wait at least one minute after power off to allow capacitors to discharge, and do not touch any
internal circuit within this period.
11. Do NOT touch internal terminals no matter power on or off.
12. For temperature accuracy, keep the controller away from heating source.
2 MODEL NAME EXPLANATION
DTC
123 45
DTC Series
DTC: Delta C series Temperature Controller
1 Controller
Position
1: first controller
2: controller in parallel
Przeglądanie stron 0
1 2 3 4 5 6 ... 11 12

Podsumowanie treści

Strona 1 - User Manual

1http://www.delta.com.tw/industrialautomation/ DTC1000/2000 Temperature Controller User Manual Thank you very much for purchasing DELTA C Series Temp

Strona 2

10Address Setting Content Explanation 1035H Executing number of reading current pattern 0~7 1037H 1000 Upper-limit of proportional output 0~100%

Strona 3 - 5 INPUT SENSOR TYPE

11 6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit data as “0”) 081

Strona 4

12To Read Instruction To Read Response Message To Write Instruction To Write Response Message Machine address 01H 01H Machine address 01H 01HMachin

Strona 5

2 2 Auxiliary Output Groups 0: standard, 2 groups output, no auxiliary output 1: 1 group auxiliary output. Not available now. 2: 2 groups auxiliary

Strona 6

34 PRODUCT PROFILE AND OUTLINE DTC1000R/V/C/L 90.03.060.03.425.24.03.01234567891031112131. RUN/STOP switch 2. Wiring and Model name 3. DIN fix 4

Strona 7 - 8 PASSWORD FUNCTION

4Note 1: an external 250Ω precision resistor is needed for current input. Note 2: factory setting: PT100 input. It is adjustable for linear input an

Strona 8 - 10 RS-485 COMMUNICATION

5PV0Dead band:deadband width:positiveDead band:deadband width:negativePV0OutputHeating CoolingSet PointOutputHeatingCoolingSet PointFigure 5: PID con

Strona 9

6value=0 with input range 0~1000, output will be 0mA or 0V. When read value=1000, output will be 20mA or 10V. Figure 7: RetransmissionOutput10V or 20

Strona 10

7SV Alarm Type Alarm Output Function value is lower than the setting value SV+(AL-L). 12 Hysteresis lower-limit alarm output: This alarm output o

Strona 11

8 Bit=0 means no password setting. Bit=1 means password is set (b0~b2). b3~b6 are used for displaying current password status. 9 SYNCHRONOUS COMM

Strona 12 - 11 INSTALLATION

9Address Setting Content Explanation Dual Loop output control are used 100FH 0 Dead band setting when Dual Loop output control are used -999~9999,