Warning
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,
installation and wiring.
Switch off the power when wiring. DO NOT tough any terminal when the power is switched on.
DVPDNET-SL is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the
device may occur.
Introduction
Functions
- Supports Group 2 server device and Group 2 only server device.
- Supports DeviceNet Master mode and Slave mode.
- Supports EDS file configure in ElinkConfigurator software.
- Supports network establishing all kinds of IO connections: polled, bit-strobe, change of state and
cyclic.
- Supports explicit connection via Predefined Master/Slave Connection Set. (explicit message)
- Offers 380 bytes for I/O input data and 380 bytes for I/O output data.
Product Profile
1
Model name
2
Extension port
3
Power, MS, NS LED
4
DIN rail clip
5
Digit Indicator
6
Extension clip
7
Address switch
8
Function switch
Unit: mm
9
DeviceNet connection port
Specifications
DeviceNet Connection
Interface Removable connector (5.08mm)
Transmission
method
CAN
Transmission cable 2-wire twisted shielded cable with 2-wire bus power cable and drain
Electrical isolation 500V DC
ENGLISH
Communication
Message type I/O polled, bit-strobe, change of state/cyclic
Baud rates
125 Kbps; 250 Kbps;
500 Kbps
Product code 64
Product type 12
Vendor ID 799 (Delta Electronics Inc.)
Electrical Specification
Module power voltage: All other power derived from PLC controller power
supply
DeviceNet
Network power input: 11 ~ 25V DC; Current: less than 50mA (25V DC)
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST
Ea)
Certificates
Installation
Dimension
3
2
0
1
4
9
8
6
7
0
MS
NS
5
DR 0
DR 1
x10
IN 1
IN 0
DVPDNET
x10
5
3
2
4
0
1
8
6
7
9
1
in millimeter and [inch]
Installing DVPDNET-SL With PLC MPU
DVPDNET DVP28SV
RUN
STOP
2
1
2
PIN Definition Of DevicetNet Connection Port
PIN Signal Color Content
1 V- Black 0V DC
2 CAN_L Blue Signal-
3 Drain - Shield
4 CAN_H White Signal+
5 V+ Red 24V DC
1
2
3
4
5
MAC ID Setting
Switch setting Content
0…63 Valid DeviceNet MAC ID setting
Others Invalid DeviceNet MAC ID setting
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
Function Switch Setting
DR1 DR0 Baud Rate
OFF OFF 125K bps
OFF ON 250K bps
ON OFF 500K bps
Retain I/O data setting
ON Retain the previous I/O data when the connection is off.
IN0
OFF Clear the previous I/O data when the connection is off.
IN1 Reserved
Cable Length and Baud Rates
The maximum cable length in a segment depends on the transmission speed. DeviceNet communicates
at speeds from 125K bps to 500K bps over distances from 100 to 500 meters.
Baud rates (bps) 125K 250K 500K
Length (m) 500 250 100
LED Indicator & Troubleshooting
There are three LED indicators and one digit indicator on DVPDNET-SL. POWER LED displays if the
power of DVPDNET-SL is working normally; NS LED and MS LED display the communication connection
status of DVPDNET-SL; digit indicator displays the node addresses, error information and the error
messages from the slave.
DVPDNET
POWER
MS
NS
POWER LED
LED Status Indication How to correct
Off Power is abnormal. Make sure the scanner is powered.
Green light On Power is normal. --
NS LED
LED Status Indication How to correct
Off
No power or duplicate ID check has
not completed
1. Make sure the scanner is powered.
2. Make sure at least 1 node or more are communicating
in the network.
Green light
flashing
No communication No correction is needed, or refer to digit-indicator.
Green light On Normal operation --
Red light flashing
Error in communication Refer to digit-indicator.
Red light On
Network error; cannot check
duplicate ID; Bus-
off (please refer to
digit-indicator)
1. Make sure all the devices have their unique address.
2. Check the network for correcting media installation
and baud rate.
3. Check if the node address of RTU-DNET is valid.
4. Check if the network power is normal.
MS LED
LED Status Indication How to correct
Off No power Make sure the scanner is powered.
Green light
flashing
The master is not configured.
Configure the scan list and re-download it to the scanner.
Green light On Normal operation
--
Red light
flashing
Some slaves encounter
communication error.
Refer to digit-indicator and check the scanner setup.
Red light On
Internal fault in the scanner module
(please refer to digit-indicator)
Check if the configuration is valid. If the internal error still
exists, replace the scanner with a new one.
NS & MS LED
LED Status
NS LED
MS LED
Indication How to correct
Off Off No power Make sure the scanner is powered.
Off Green
Duplicate ID check has not
completed.
Make sure at least 1 node or more are communicating in
the network and the baud rate is the same as the setting
in DVPDENT.
Red Green
MAC ID detection failure or
Bus-off
Change the MAC ID setting and re-power DVPDNET.
Red Red flashing
No 24V DC power from
DeviceNet network
Check if the network cable is correctly connected to
DVPDNET. Check the 24V DC network power.
Red Red
Hardware error and no net
power
Go to your manufacturer or distributor for
problem-solving.
Digit Indicator LED
Code
Indication How to correct
0 ~ 63
Node address of scanner, normal operation --
F0 Duplicate MAC ID check failure Change the address and re-power DNET scanner.
F1 No scan list is active in the module
No slave device in the scan list. Configure the scanner
and download it to the scanner.
F2 Low voltage is detected
Check if the power of the scanner and PLC MPU is
normal.
F3 Entering Test Mode Switch IN1 from ON to OFF and re-power the scanner.
F4 Bus-off detected
1. Check if the network cable is normal.
2. Check if the baud rate is correct.
3. Re-power the scanner.
F5 No network power
Make sure the cable is correctly connected and check if
the network power is normal.
F6 Internal error; Flash or Ram check error
If the error still exists after re-power, replace the scanner
with a new one.
F7 Internal error; GPIO check error
If the error still exists after re-power, replace the scanner
with a new one.
F8
Error in factory manufacturing
If the error still exists after re-power, replace the scanner
with a new one.
F9 Internal error; EEPROM access failure
If the error still exists after re-power, replace the scanner
with a new one.
E0
Device key parameter does
not match scan list
table.
Make sure that the device parameter in scan list matches
the desired key parameter, including vendor ID, product
code, device type and version.
E1 Data size returned does not match scan list. Re-configure scan list using correct data size.
E2 Salve device in scan list does not exist.
The desired slave device does not exist in the network.
Add device to the network.
E3 Module fails to transmit a message
Make sure that the connection is valid and check if the
baud rate is correct.
E4
Error detected in sequence of fragmented I/O
messages from device.
Fragmented I/O data is invalid from slave device.
E5
Slave device returns error response when the
scanner attempts to communicate with it.
Check if the salve is normal.
E6
Data size returned is bigger than expected.
Check slave device configuration and scan list
configuration.
E7
Device is checking MAC ID.
No correction is needed, or check if the network
connection is normal.
(OPEN TYPE)
- (Group 2 server) (Group 2 only server)
- DeviceNet
- ElinkConfigurator EDS
- IO (Polled) (Bit-Strobe) (Change of State)
(Cyclic)
- /
- 380 I/O 380 I/O
1
2
3
Power, MS, NS
4
DIN
5
6
7
8
mm
9
DeviceNet
DeviceNet
(5.08mm)
CAN
2 2 1
500V DC
I/O
125 Kbps; 250 Kbps; 500 Kbps
64
12
ID
799 (Delta Electronics Inc.)
PLC
DeviceNet
11 ~ 25V DC 50mA (25V DC)
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0ºC ~ 55ºC 50 ~ 95% 2
-40ºC ~ 70ºC 5 ~ 95%
/ IEC1131-2 IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
3
2
0
1
4
9
8
6
7
0
MS
NS
5
DR 0
DR 1
x10
IN 1
IN 0
DVPDNE T
x10
5
3
2
4
0
1
8
6
7
9
1
mm [inch]
Przeglądanie stron 0
1 2

Podsumowanie treści

Strona 1 - DVPDNE T

Warning  This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation and wiring.  Sw

Strona 2 -  (OPEN TYPE)

PLC DVPDNET-SL DVPDNET DVP28SVRUNSTOP212  DevicetNet 1 V- 0V DC 2 CAN_L Signal- 3 Drain - 4 CAN_H Signal+ 5 V+ 24V DC 12345

Komentarze do niniejszej Instrukcji

Brak uwag