Series EL Series E Series
single phase 3 phase 3 phase
model number VFD-__EL/E/C
002 004 007 015 004 007 015 022 037 004 007 015 022 037 055 075 110 150 185 220
frame size
- - - - - - - - - - - - - - - - - - - -
max. applicable motor output kW
0.2 0.4 0.75 1.5 0.4 0.75 1.5 2.2 3.7 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Output rating
rated output capacity
NORMAL DUTY
kVA
0.6 1 1.6 2 1.2 2 3.3 4.4 6.8 1.2 2 303 404 6.8 9.9 13.7 18.3 24 29 34
rated output current A
1.6 2.5 4.2 7.5 1.5 2.5 4.2 5.5 8.2 1.5 2.5 4.2 5.5 8.5 13 18 24 32 38 45
output frequency Hz
setting range 0.1 – 600Hz 0.1 – 600Hz
carrier frequency kHz
2 – 12kHz 1 – 15 kHz
rated output capacity
HEAVY DUTY
kVA
- - - - - - - - - - - - - - - - - - - -
rated output current A
- - - - - - - - - - - - - - - - - - - -
carrier frequency kHz
- - - - - - - -
-
- - - - - - - - - - -
Input rating
input current (heavy duty) A
- -
input current (normal duty) A
4.9 6.5 9.5 15.7 1.8 3.2 4.3 7.1 9 1.9 3.2 4.3 7.1 11.2 14 19 26 35 41 49
rated voltage V
1-phase AC 200 – 240V 3-phase AC 380V – 480V 3-phase AC 380V – 480V 50/60Hz
operating voltage range V
180 – 264V ±10% 342 – 528V ±10% 342 – 528V ±10%
frequency tolerance Hz
± 5% (47 – 63Hz) ± 5% (47 – 63Hz)
cooling method
convection fan convection fan cooling convection fan cooling
braking chopper
- built-in
DC reactor
- -
control method
SPWM (Sinusoidal Pulse Width Modulation) V/f control SPWM (Sinusoidal Pulse Width Modulation) V/f control
Starting torque %
up to 150% at 5.0Hz including auto-torque/slip up to 150% at 3.0Hz including auto-torque/slip compensation
V/f Curve
adjustable V/f pattern adjustable V/f pattern
torque limit %
150% -
Max. output frequency Hz
three zones, setting range 0.1 – 600Hz 0.1 – 600Hz
frequency output accuracy
- -
frequency setting resolution Hz
0,01Hz 0.01Hz
overload tollerance
150% of rated current for 1 minute 150% of rated current for 1 minute
frequency setting signal
pot-5k/0.5W, 0 – +10Vdc, 4-20mA RS-485 interface pot-5k/0.5W, 0 – +10Vdc, 4 - 20mA, RS-485 interface
accel./decel. Time
0.1 – 600 sec. (2 settings accel/decel time) 0.1 – 600 sec. (2 independent settings accel/decel time)
main control functions
AVR, accel/decel S-Curve, overvoltage/curren
tstall prevention, 5 fault records, reverse inhihition,
momentary power loss restart, DC braking, auto torque/
slip compensation, adjustable carrier frequency, output
frequency limits, PID control, external counter
built-in PLC, AVR, accel/decel S-Curve, over-voltage/current stall prevention,
5 fault records, reverse inhibition, momentary power loss prevention, DC braking,
auto torque/slip compensation, auto tuning, output frequency limits, vector control,
PID control, external counter, MODBUS communication, abnormal reset/restart,
adjustable carrier frequency, power saving, fan control, NPN/PNP selection
fan control
fan control fan control
motor protection
electronic thermal relay protection over/under-volt/current, ext. fault, overload, IGBT short circuit, PTC
over-current protection
yes yes
over-voltage protection
yes yes
over-temperature protection
yes yes
stall prevention
20 – 250% of rated current 20 – 250% of rated current
re-start after momentary power off
yes yes
ground current protection
yes yes
EMI lter
built-in built-in
dimensions
H mm
174 174 174 174 142 174 260 310
W mm
72 100 72 100 72 100 130 200
D mm
136 136 136 136 152 152 169 190
optional accessories
CANopen/Devicenet/LONworks/PROFIBUS modules CANopen/Devicenet/LONworks/PROFIBUS modules
braking unit, brake resistors, DIN rail mount adaptor analogue I/O cards - relay cards - PG card, brake resistors
DIN rail mount adaptor - digital keypad