DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 8 4.3 DFROM & DTO Instructions 1. DVP-EH2 PLC MPU reads or writes d
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 9Program example Write the content in D10 and D11 into CR#3 and CR#4 of s
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 10 of the master. When DVPPF02-H2 is used as PROFIBUS DP slave, you have
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 11¡ Establishing PROFIBUS DP network by DVPPF02-H2 (hardware configuratio
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 12 3. Click on “Next”. 4. Select CPU of S7-300 and click on “Next&quo
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 13 5. Select the block and the language for selected block, and click on
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 14 7. You will then see a new window indicating that a new project has
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 15 2. In the “HW Config” window, double click on “DP” in the table of th
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 16 4. Select “Address” as the address of the master. Next, click on “Ne
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 17 6. Once all the parameters are set, a PROFIBUS DP bus will be created
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 18 2. Find the path of the GSD file, select the GSD file to be installe
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 19 Creating DVPPF02-H2 slave and parameter configuration 1. Select PRO
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 20 4. Select “Slot 0" and double click on “2 Word Out” in the righ
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 21 6. Configure parameters of other slots in the same way. Note: DVPPF0
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 22 (e.g. the configuration of slot 0, slot 1). The maximum length of tota
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 23 4. After the download is completed, the NET LED on DVPPF02-H2 will be
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 24 Slot External I/O word for S7-300 Data transmission direction in PROFI
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 25Slot External I/O word for S7-300 Data transmission direction in PROFIB
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 26 MEMO
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 1 Warning 3 Please read this instruction carefully before use and follow
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 2 6 LED INDICATORS & TROUBLE-SHOOTING...
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 31 Introduction 1. To ensure correct installation and operation of DVPPF
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 4 2 Product Profile & Outline 2.1 Dimension POWE RNETX16X16 Unit: mm
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 5STOP RUN01 INOUTPOWERRUNERRORBAT.LOWDVP-20EHx160x161 2.4 Installing DVP
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 6 2.6 Installation & Wiring 1. Install DVPPF02-H2 in an enclosure wi
PROFIBUS DP Slave Communication Module DVPPF02-H2 DVP-PLC Application Manual 73.3 Transmission Distance & Baud Rate The communication speed in PR